Ryan Sales logo
(281) 363-1106
Home
TJNT140 Transition Joints

TJNT140 Transition Joints

For joining oil filled cable to extruded dielectric cable systems through 145 kV. G&W Electric’s type TJNT140 joints are ideal for direct buried or enclosed vault applications. The joints utilize precision prefabricated components offering many advantages over conventional tape and other joint designs. Joints are designed and tested in accordance with applicable sections of IEC 60840 and IEEE 404. Designs include transition joints for low pressure fluid filled (LPFF) and high pressure fluid filled (HPFF) cable.

Features and Benefits

  • More economical than replacing entire cable runs with modern extruded dielectric cable.
  • Allows phase-in of extruded dielectric cable over several months or years.
  • Ability to terminate oil cable and extruded cable side independently.
  • Available with fiberglass enclosure and filling compound.
  • Disconnectable, permitting easier future replacement of oil cable with extruded cable without cutting connectors or pulling additional cable.
  • Suitable for vault or direct burial applications.

Configuration:

Extruded Solid Dielectric Cable Side Range: 500kcmil – 2500kcmil, LPFF Side Range: 500 kcmil – 2250kcmil, Copper or Aluminum Conductor

 

Ratings:

Voltage: 115kV-145kV, Basic Impulse (BIL) 650kV