Texas & Oklahoma utilities and infrastructure since 1984Data center projects nationwide Find your repAbout(281) 363-1106Request a quote
Ryan Sales — Medium & High Voltage Specialists Get a quoteQuote
Underground & Cable

Transmission Cable Accessories

Ryan Sales supplies G&W Electric high voltage cable termination and joint systems for transmission cable from 69kV through 500kV IEEE. The line covers outdoor, GIS and transformer terminations, premolded joints and accessories for legacy pipe-type and fluid-filled systems, with rep support for transmission utilities and EPCs in Texas and Oklahoma.

Substation equipment

Not sure which one fits?

Send the voltage, ampacity and fault duty. A rep will narrow it down.

G&W Electric ATA/ATL Outdoor Terminations, through 345kVG&W ElectricATA/ATL Outdoor TerminationsOutdoor terminations for self-contained fluid-filled and pipe-type transmission cable systems through 345kV.
Maximum voltage
Through 345 kV
Cable systems
HPFF / LPFF / SCOF
Configuration
Outdoor / GIS (SF) variants
Details
G&W Electric LPP Joints, through 345kVG&W ElectricLPP JointsCable joints for self-contained and pipe-type transmission systems through 345kV.
Maximum voltage
Through 345 kV
Cable systems
Self-contained / pipe-type
Details
G&W Electric PAT130C Dry Type Outdoor TerminationG&W ElectricPAT130C Dry Type Outdoor TerminationPremolded dry-type outdoor termination for 115-138kV solid dielectric cable with mechanical shrink installation.
Voltage class
110–145 (IEC) / 115–138 (IEEE) kV
Conductor range (copper)
240–1600 mm²
Conductor range (aluminum)
240–1200 mm²
Details
G&W Electric Python Outdoor PAT Style TerminationG&W ElectricPython Outdoor PAT Style TerminationPorcelain-insulated outdoor terminations for solid dielectric transmission cable through 345kV.
Voltage class
72.5–362 (IEC) / 69–345 (IEEE) kV
Insulation
Porcelain insulators with anti-flashover sheds
Installation
Mechanical shrink technology
Details
G&W Electric Python PATR Style GIS and Transformer TerminationsG&W ElectricPython PATR Style GIS and Transformer TerminationsGIS and transformer-compatible terminations for solid dielectric transmission cable.
Voltage class
72.5–362 (IEC) / 69–345 (IEEE) kV
Configuration
GIS / transformer interfaces
Installation
Premolded, mechanical shrink
Details
G&W Electric Python Premolded JointsG&W ElectricPython Premolded JointsFactory-molded, 100% routine-tested splices for XLPE and EPR transmission cable through 500kV.
Voltage class
72.5–550 (IEC) / 69–500 (IEEE) kV
Routine testing
100% routine tested
Installation
Mechanical shrink
Details
G&W Electric SSC160 Plug-in/Plug-out Dry GIS and Transformer TerminationG&W ElectricSSC160 Plug-in/Plug-out Dry GIS and Transformer TerminationDry, plug-in/plug-out GIS termination with visual disconnect that prevents accidental disconnection through 500kV.
Voltage class
145–550 (IEC) / 138–500 (IEEE) kV
Plug-in/plug-out voltage
Up to 245 (IEC) kV
Conductor range
240–2500 (copper or aluminum) mm²
Details
G&W Electric TJNT140 Transition Joints, through 138kVG&W ElectricTJNT140 Transition JointsTransition joints connecting dissimilar transmission cable systems through 138kV.
Maximum voltage
Through 138 kV
Configuration
Transitions between cable system types
Construction
Premolded
Details

How to choose transmission cable accessories

Cable system: solid dielectric or fluid-filled

The cable technology already in the ground decides the product family. New transmission circuits are almost all solid dielectric XLPE or EPR, served by the Python and PAT families. Legacy high-pressure fluid-filled (HPFF), low-pressure fluid-filled and self-contained fluid-filled circuits need accessories built for those systems: ATA/ATL Outdoor Terminations and LPP Joints both run through 345kV.

Termination interface: outdoor, GIS or transformer

Define where the cable ends before choosing the termination. An overhead-to-underground transition or open-air substation uses an outdoor termination; the Python Outdoor PAT Style Termination covers 69 to 345kV with porcelain insulators. For 115 to 138kV, the PAT130C Dry Type Outdoor Termination uses a dry premolded body, which removes insulating fluid from the termination. Connections into gas insulated switchgear or a transformer use the Python PATR, or the SSC160 Plug-in Dry GIS and Transformer Termination to 500kV, with plug-in/plug-out available to 245kV IEC so the cable can be separated from the GIS for testing or maintenance.

Product Interface IEEE voltage Cable
PAT130C Outdoor, dry 115-138kV XLPE, EPR
Python PAT Outdoor, porcelain 69-345kV XLPE, EPR
Python PATR GIS / transformer 69-345kV XLPE, EPR
SSC160 GIS / transformer, dry plug-in 138-500kV Copper or aluminum, 240-2500mm2
ATA/ATL Outdoor and GIS Through 345kV HPFF, LPFF, SCOF

Voltage class and qualification testing

Match the accessory's rating to the system voltage and confirm it carries the type and prequalification testing the utility requires. Python Premolded Joints are prequalification and type tested per IEC 62067 at 230, 345 and 500kV and 100% routine tested at the factory. Check conductor size and insulation diameter as well, since premolded bodies fit a defined range.

Joints and transitions

Where a circuit mixes old and new cable, a transition joint avoids replacing the whole run. TJNT140 Transition Joints connect dissimilar cable systems through 138kV, letting a utility splice new XLPE into a legacy circuit during upgrades or repairs. On fluid-filled systems, LPP Joints serve the same splicing role through 345kV and support ongoing maintenance of circuits that are not yet due for replacement. Bring the existing cable data, including conductor size, insulation type and any as-built records, to the first conversation so the transition can be engineered correctly.

There are no dedicated articles for this category yet; see our cable splices and terminations for distribution-class accessories.

Frequently asked questions

Dry vs fluid-filled outdoor terminations?

Dry outdoor terminations use a premolded rubber stress cone with no insulating fluid, and fluid-filled terminations surround the stress cone with oil or silicone fluid inside an insulator. Dry designs remove leak risk and fluid maintenance and are faster to install. Fluid-filled designs have a long track record at the highest voltages. G&W's PAT130C is a dry outdoor termination for 115 to 138 kV, and its ATA/ATL terminations serve fluid-filled pipe-type systems through 345 kV.

What is a plug-in GIS termination?

A plug-in GIS termination connects high voltage cable to gas-insulated switchgear by plugging a prepared cable end into an insulator already installed in the GIS. The GIS and the cable can therefore be installed and tested separately, and the cable can later be unplugged without opening the gas compartment. G&W's SSC160 is a dry termination that plugs in and out up to 245 kV IEC and meets IEC 62271-209.

Can you joint XLPE to pipe-type cable?

Yes. XLPE cable can be jointed to pipe-type cable, such as HPFF cable, with a transition joint. The joint connects the conductors and seals off the pressurized dielectric fluid on the pipe-type side, so the solid-dielectric XLPE side stays dry. It also controls electrical stress at both insulation systems. This is often done when a utility replaces part of an aging pipe-type circuit. G&W's TJNT140 transition joints handle this through 138 kV, and its LPP joints serve pipe-type systems through 345 kV.

Often specified with

Request a quote Call